Elevator 1:
Trouble call;
-
187
-
188
-
130 5000 41
-
130 5000 52
-
130 5100 225
-
2703
-
Replaced BCM25 brake module
-
Loose wire @ 464:3 [14]
-
Loose wire junction box XM12 (remote yellow # 4 - unrelated to current issue)
-
Replaced E-brake proximity switch
-
LCEOPT board misconfiguration, remedied.
-
GC had a chance to ride elevator before we left.
-
As requested by the GC, departed leaving elevator on the 1st floor, independent service, stop switch engaged.
Elevator 2:
Not in service, notes for when we are sent back;
-
Troubleshoot zone from video
-
2703 LCEOPT board 1 front needs to be changed to a 2 rear.
Quick walk-through stats:
Machine room needs:
-
Fire extinguisher
-
Heat detector and shunt trip need to be installed (or sprinkler removed)
-
-
Door does not latch when closed.
-
4 wires from transfer switch for emergency power.
-
Phone lines brought into controllers.
-
Layouts are missing.
Lobbies:
- Lighting;
-
Most floors are around 4fc at the sill. They need to be 10fc.
-
Most if not all have motion lights. Motion sensors must pick up door movement and the sill must be at required foot-candles by the time the door is open.
- LL;
- Security switched have not been installed. Flex for them is protruding through finished walls at an inconvenient height.
- 1st floor;
-
Car designation placard needs to be installed on E1 rear. GC has foam padding installed currently preventing this.
-
Lobby phone needs to be wired in. Lobby phone box is protruding out of the wall.
-
Emergency power box needs to be wired in.
-
E1 rear PI is not installed.
-
Couple of PI and PB screws are missing from front and rear.
-
Firebox.
- Smoke detectors;
- Still need to check height to ensure detectors are not over 15'.